Title
Non-Uniform Field Breakdown of Ar +SF6 under Negative Polarity Impulse Voltages
Document Type
Conference Proceeding
Publication Date
10-26-2008
Publication Title
IEEE Xplore
Conference Name
2008 Annual Report Conference on Electrical Insulation and Dielectric Phenomena
Abstract
In this study, negative-polarity, standard lightning impulse voltages with different magnitudes were employed throughout the experiments. The percentage of SF 6 in Ar was varied from 1% to 90% and from 1% to 75% at a total gas pressure of 50 kPa and 100 kPa, respectively. The breakdown voltage of each gas mixture was recorded at 50% breakdown probability. Similar to earlier studies under static electric fields it is observed that the breakdown voltages of Ar+SF 6 has increased dramatically when mixed with a small percentage of SF 6 under impulse voltages. However, the breakdown voltages were found to be higher than positive polarity, non-uniform and uniform fields.
Rights Statement
This is a RoMEO green publisher - Must link to publisher version
© Copyright 2008 IEEE
Recommended Citation
Hiziroglu, Huseyin R. and Dincer, M. S., "Non-Uniform Field Breakdown of Ar +SF6 under Negative Polarity Impulse Voltages" (2008). Electrical & Computer Engineering Presentations And Conference Materials. 42.
https://digitalcommons.kettering.edu/electricalcomp_eng_conference/42
Comments
Quebec, QC, Canada