Title
Breakdown of Ar + SF6 under ac electric fields
Document Type
Conference Proceeding
Publication Date
10-17-2010
Publication Title
IEEE Xplore
Conference Name
2010 Annual Report Conference on Electrical Insulation and Dielectric Phenomena
Abstract
In this study, alternating voltages with different values were employed to study the behavior of Ar mixed with SF 6 . The percentage of SF 6 in Ar was varied from 5% to 90% at a total gas pressure of 50 kPa, 100 kPa, 150 kPa and 200 kPa, and the breakdown voltages of each gas mixture were recorded. Similar to earlier studies under static electric fields and impulse fields, it is observed that the breakdown strength of Ar has increased dramatically when mixed with a small percentage of SF 6 under alternating voltages. However, the breakdown voltages did increase monotonically, but not dramatically for higher SF 6 concentrations in Ar.
Rights Statement
This is a RoMEO green publisher - Must link to publisher version
© Copyright 2010 IEEE
Recommended Citation
Hiziroglu, Huseyin R. and Dincer, M. S., "Breakdown of Ar + SF6 under ac electric fields" (2010). Electrical & Computer Engineering Presentations And Conference Materials. 38.
https://digitalcommons.kettering.edu/electricalcomp_eng_conference/38
Comments
West Lafayette, IN, USA